UHV(L) Inductance Adjustable Power Frequency AC Resonance Test System



 





 




Technical Parameter


 




































Rated output voltage



0~60kV (AC rms) and below



Output frequency



50Hz



Resonant voltage waveform



Pure sine wave, waveform distortion rate ≤1%



Work system



Full power continuous working time 1min



Quality factor



10~40



Maximum test capacity



3000kVA and below



Working power supply



380V±15%, power frequency 50Hz




 



Series product configuration (scope of application (AC withstand voltage test of generator or motor with outlet voltage 20kV and below, test frequency: 50Hz))






























































Product model



Control Console



voltage regulator



Reactor (dry)



Excitation change (dry)



Voltage divider



Scope of application



HTXZ(L)- 200kVA/25kV



30kW



30kVA (electric)



200kVA/25kV adjustable one



30kVA dry



30kV



Hydroelectric generator. 0.4~1.0μF.(10kV/40MW)



HTXZ(L)- 300kVA/50kV



60kW



60kVA (electric)



300kVA/50kV adjustable one



60kVA oil



50kV



Thermal generators.0.27~0.33μF.(20kV/300MW)



HTXZ(L)- 600kVA/50kV



60kW



60kVA (electric)



200kVA/50kV adjustable one 400kVA/50kV adjustable one



60kVA oil



50kV



Thermal generators.0.113~0.45μF.(20kV/600MW)



HTXZ(L)- 1200kVA/50kV



120kW



120kVA (induction)



200kVA/50kV fixed two 800kVA/50kV adjustable one



120kVA oil



50kV



Hydroelectric generator.0.6~1.8μF.(20kV/250MW)



HTXZ(L)- 2750kVA/55kV



300kW



300kVA (induction)



750kVA/55kV fixed two 1250kVA/55kV adjustable one



120kVA oil



60kV



Hydroelectric generator.1.6~3.3μF.(20kV/770MW)





Note: The solution can be customized according to the sample object parameters



 



Reference table of the capacity of hydroelectric generators commonly used in power systems







































Hydroelectric generator



Rated capacity (WM)



Rated voltage(kV)



Phase capacitance(μF)



72.5~85



10.5



0.694



125~150



/



1.8~1.9



300



15.75



1.7~2.5



400



18.0



2~2.5



600



/



2.1~2.5




Nickname: Resonance System; Resonance Test System; AC Resonance Test; Resonance Test





 





 




Feature


 



1. Due to the full compensation of reactive power resonance, the power supply and equipment are only less than 1/10 of the required capacity of the tested product (1/Q10); The same capacity is small in size, light in weight, the output capacity of the device is large and the power capacity required for configuration is small, the price is low, and the operation is convenient and safe.



2. Series resonance is actually a current filter loop, so that the current passing through the test product is basically the fundamental current, and the waveform distortion rate (THD) of the output voltage is extremely small, which is better than all types of existing AC withstand voltage equipment.



3. The short-circuit current after flashover or breakdown of the sample is only less than 1/10 of the test current before the short circuit (1/Q), which can effectively prevent the expansion of damage to the fault point after breakdown.



4. Immediately after flashover, the arc is automatically extinguished, and the process of restoring the resonant state voltage establishment after arc extinguishing is long (seconds) is a steady-state establishment process, and there is no concern about voltage overshoot, nor the danger of recovery overvoltage in the microsecond-level millisecond-level transient process.



 





 



 





 



 



Q: What is resonance of a system?

A: A phenomenon in which an external force or a vibrating system forces another system around it to vibrate with greater amplitude at a specified frequency of operation.



 



Q: What is the effect of resonance in a system?

A: The most important effects of resonance can be listed as follows: The voltages for capacitive and inductive system components increase. As a result, inductive and capacitive system components draw overcurrent. The isolation of the circuit components becomes challenging.



 